Searching for a way to improve the performance of your electrical system? Seek no more as Dadao has got your back with its SDK192I Single-phase Ammeter. This digital panel meter hails from a Chinese manufacturer with an outstanding reputation for quality. Get the Dadao upgrade today and witness the transformation. Reach out today for further insights and pricing.

Save a minimum of 35% or more on your purchases.

Digital Panel Meter:SDK192I- Single-phase Ammeter
Digital Panel Meter:SDK192I- Single-phase Ammeter

Functional features of SDK192I- Single-phase Ammeter

SDK19 series programmable single-phase current and voltmeter utilize specially designed power measurement chip in conjunction with microcontroller circuitry; this product is 4 digit with pretty good accuracy and dependable. The performance of the device can be user configured. It consists of limit settings for operate the meter using the key surface, alarm return, alarm action and the value of alarm return.

Technical chart

Main ItemsMain ItemsTechnical Parameter
Input SignalCurrent SignalAC Current 0-5A Through, Continuous Operation 1.2 Times, Instantaneous 10 Times / 1 Second, ≥6A Need To Use Current Transformer
DC Current 0-5A Through, Continuous Operation 1.2 Times, Instantaneous 10 Times / 5 Seconds, ≥6A Or More Need To Use Current Shunt
Voltage SignalAC Voltage 0-500v, Continuous Operation 1.2 Times, Instantaneous 2 Times/sec, ≥ 600V Need To Use The Voltage Transformer
DC Voltage 0-500v, Continuous Operation 1.2 Times, Instantaneous 2 Times / I Seconds
Frequency45-65hz
Input ImpedanceVoltmeter >500kω, Ammeter <2mω
Measured VoltageDisplay Range0-9999, Four-Digit Led Digital Tube Display
AccuracyCurrent/Voltage: 0.5 Level; True Rms Measurement With Fluctuations Of Plus Or Minus One Word.
Unit SelectionMeter Unit "K" (Kilograms) Is Set By The Software And Indicated By The Indicator.
Ac And Dc IndicationAc/Dc Signal Input Indication (Above The Unit Symbol On The Panel, Light Is On For Dc Signal, Not On For Ac)
Additional FunctionalityAlarm Output1 Dry Junction Relay Output, Contact Ac220v 50hz 1a (Resistive).
NewsletterRs485 Communication, M0dbus-Rtu Protocol
Power SupplyAc220v 50hz (Special Voltage Can Be Customized), Power Consumption ≥ 2va
OtherSafety PerformanceInsulation Resistance ≥ 100mω, Frequency Withstand Voltage: 2kv1min Ac Rms Value
Current SignalWorking Temperature: 0-50°C Relative Humidity ≤90% No Corrosive Gas Occasions

Model Description

Model Description

Technical chart

Related products

Dadao's latest blog

To stay relevant to your interests, do not miss out on Dadao’s latest blog for recommendations and insights.

Hi. How can we help?
Discover articles, guidance, and expert advice.

or write in

Scroll to Top
Get in touch with Dadao Electric Co.,Ltd
Contact Form used